Back To Top
DeltaV™ CTO CHARM Field Enclosures
PDP_DeltaV CTO CHARM Field Enclosures
The DeltaV™ Configure To Order (CTO) CHARM Field Enclosures provide an off-the-shelf solution for faster project execution and reduced installation costs.
Field Enclosures are factory tested products and ready for installation in the field. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before control strategies are finalized.
DeltaV™ CTO CHARM Field Enclosures

Specs

Material
Stainless Steel SS304 (316L Optional) Enclosure Thickness 2.5mm
Dimensions
96 IO - 915mm (W) x 1220mm (H) x 475mm (D)
48 IO/ D96 - 915mm (W) x 1070mm (H) x 325mm (D)
Access
Front- Single door, left hand hinged
Protection Category
IP 66/ IP64 – NEMA 4X (Corrosive Environment)
Cable entry
Bottom, single gland plate (Thickness 3mm) ( Cable Glands, Transit Frames Optional)
Weight
~165 kg (may vary as per hardware added by option selection)
Power Requirements
Redundant distribution through power terminals Main Switch OptionaL):
100-120 VAC 50/60 Hz
220-240 VAC 50/60 Hz

Configured with one of the following internal power supply systems:
2x 5A and full redundant (primary and secondary) 24 VDC distribution
2 x 10A and full redundant (primary and secondary) 24 VDC distribution
2 x 20A and full redundant (primary and secondary) 24 VDC distribution
Control Network
Configured with one of the following control network systems:
Redundant Single Mode FO with Media Converter
Redundant Multi-Mode FO with Media Converter
Redundant Copper (RJ45)
IO Count / Type
Up to 96 IO
DCS - CIOC with Non IS, IS IO Charms

Distributed Charms:
CIOC with Non IS, IS Charms, DCS external 12 CHARM IO Junction Box
Name Plate
Outside Door: Laser engraved plastic
Environmental Specification
Outdoor installation
-20 to +36 ° C (-4 to 96.8° F) Safe Area ASCO VLV
-40 to 50° C (-40 to 122° F)
-20 to 55° C (-4 to 131° F) (Only for IECEx, ATEX, CE)
Relative humidity
5-95% (non-condensing)
Globally Certified
Global: IECEx
Europe: Zone 2 - ATEX, CE,
North America: cCSAus - Haz. Loc:Class 1 Div.2, Ordinary Location,
China: Zone 2, 22, NEPSI, CCC
Shock
10 g½-sine wave for 11 ms
Vibration
1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz

Features

  • Delivers Electronic Marshalling enabled by CHARMs technology
  • Reduces system footprint
  • Eliminate I/O home run cables
  • Fully documented package
  • Significantly reduce cabinet design engineering