Certifications and Compliances
cCSAus Certified: Ordinary Locations
Material
Fiberglass reinforced, carbon impregnated, UV resistant polymer
Ambient Temperature
-40 °C to + +60 °C (-40 °F to +140 °F); Starting at -20 °C (-4 °F)
Temperature Input
Range: 0 °C to +218°C (+32°F to +425°F). Accuracy: ±1 °C. Repeatability: ±1 °C. RTD: 100-ohm platinum, 3W, (sold separately)(lead compensated up to 20 ohms)
Heater Switching
Configuration: Two-pole, EMR. Ratings: 100-277 Vac, 30 Amp continuous (resistive load only). Line Frequency: 50 or 60 Hz
Control Power
Power Requirement: Control power from heater voltage, 110-277 Vac, 12 VA max
User Interface
The single line, alphanumeric LCD display enables the use of English language prompts for setpoint entry and operation. There are no cryptic codes or key press combinations to remember
Enclosure
6.5"H x 6.5"W x 4.0"D, captive screw covers
Alarm Output
Alarm: EMR Form C. Alarm Rating: EMR Version 24-277 Vac @ 2.0 Amp Max, 12-30 Vdc. Alarm Output: LED Indication
Alarm Function
High Temperature Alarm, Low Temperature Alarm, Sensor Failure, Ground Fault Trip